NYCWY 0,6/1kV 3x120/70 mm2

NYCWY 0,6/1kV 3x120/70 mm2

Filkab SKU: 100546159810
List price
Euro.,VAT excl.
Number of Wires 3
Cross-section of Wires 120
Nominal Voltage Uo/U, kV 0,6/1kV
Insulation PVC
Conductor Material Cu
Test Voltage AC, kV 4kV
min Ambient Temperature, °C -30°
max Ambient Temperature, °C +50°
min Temperature of Laying, °C -5°
CPR Class Eca

Power cable, Cu-conductor, PVC-insulation, Cu-concentric conductor
Application - Power cable for construction of underground supply and distribution grids and installations of industrial and public projects, for street lighting, suitable for transmission and distribution of electric power at nominal voltage UO/U 0,6/1 kV. The corrugated concentric conductor type CW is not cut off when tapping the electric network and is like a screen, could be used as neutral (N), earthing (PE), and both as neutral and earthing (PEN) conductor.

Construction -
Solid or stranded Cu wires cl.1 or cl.2 acc. to DIN VDE 0295
Insulation: PVC compound
Colour coded: to VDE 0293-308 and HD 186
Inner sheath: filling compound
Screen: concentric conductor (Ceander) of Cu wires and one or two helically applied Cu tapes
Outer sheath: PVC compound
Outer sheath colour: black

Technical data -
Power cable acc. to VDE 0276-603, 7-cores and above acc. to VDE 0276-603
Ambient temperature: -30°С - +50°С
min Temperature of laying: -5°С
max Operating temperature: +70°С
Short circuit temperature: +160°С (short circuit duration up to 5 sec.)
Nominal voltage UO/U: 0,6/1 кV
Test voltage: АС – 4 кV/50Hz, DC – 12 kV
Min. bending radius: for single core - 15 x D, for multi-core - 12 х D
Flame-retardant: VDE 0482-332-1-2/IEC 60332-1-2
CPR Class: Eca

*The cable diameters are approximate. The cable diameters may vary depending on the cable producer, and in accordance with the stated standard.