NYCY 0,6/1kV 3x10/10 mm2
NYCY 0,6/1kV 3x10/10 mm2
Euro.,VAT excl. 10.75 €/M
Power cable, Cu-conductor, PVC-insulation, Cu-concentric conductor
Application - Power cable suitable for construction of underground supply and distribution grids and installations of industrial and public projects, for street lighting, for transmission and distribution of electric power at nominal voltage UO/U 0,6/1 kV. The concentric conductor is used as a screen and could be used as neutral (N), earthing (PE), and both as neutral and earthing (PEN) conductor, but not as an external conductor.
Construction -
Solid or stranded Cu wires cl.1 or cl.2 acc. to DIN VDE 0295
Insulation: PVC compound
Colour coded: to VDE 0293-308, VDE 0276 part 603 or HD 186
Inner sheath: filling compound
Concentric conductor of Cu wires and helically applied Cu- tape
Wrapping: polymer tape
Outer sheath: PVC compound
Outer sheath colour: black
Technical data -
Power cable acc. to VDE 0276-603, 7-cores and above acc. to VDE 0276-627
Ambient temperature: -30°С - +50°С
min Temperature of laying: -5°С
max Operating temperature: +70°С
Short circuit temperature: +160°С (short circuit duration up to 5 sec.)
Nominal voltage UO/U: 0,6/1 кV
Test voltage: АС – 4 kV/50Hz, DC – 12kV
Min. bending radius: for single core - 15 x D, for multi-core - 12 х D
Flame-retardant: VDE 0482-332-1-2/IEC 60332-1-2
CPR Class: ECa
*The cable diameters are approximate. The cable diameters may vary depending on the cable producer, and in accordance with the stated standard.